Strut Channels (Unistrut)
Unistrut catalogueCold-formed slotted-lip channel for services, pipe and cable supports, frames and brackets. Dimensions per Unistrut's catalogue. Dimensions, section properties, AS 4100 capacities and free DXF drawings for all 2 sizes.
Strut channel (often called by the brand name Unistrut) is a cold-formed channel whose lips turn in and back to leave a continuous slot. Spring nuts and channel nuts drop into the slot anywhere along the length, so the channel is used for services supports, pipe and cable tray hangers, trapezes, equipment frames and brackets without drilling or welding.
The sizes here are the 2.5 mm plain (unslotted) channels: P1000 is 41 × 41 mm and P3300 is the shallow 41 × 21 mm. Dimensions follow Unistrut's catalogue, and the calculated properties agree with its published values within about 1.5%. Slotted (T) versions have holes punched along the back, which reduces their area and stiffness. Unistrut is a trademark of Atkore; other makers' strut channel has similar but not identical dimensions.
Select any section in the table to open its page, with a dimensioned drawing, all section properties and a free DXF download for your CAD software.
| Designation | Mass kg/m | D mm | B mm | t mm | Ag mm² | Ix 10⁶mm⁴ | Zx 10³mm³ | Sx 10³mm³ | Iy 10⁶mm⁴ | ry mm | J 10³mm⁴ |
|---|---|---|---|---|---|---|---|---|---|---|---|
| P1000 | 2.88 | 41.3 | 41.3 | 2.5 | 333 | 0.0912 | 4.42 | 5.22 | 0.0708 | 14.6 | 0.694 |
| P3300 | 1.91 | 41.3 | 21 | 2.5 | 232 | 0.0530 | 2.56 | 3.25 | 0.0121 | 7.2 | 0.482 |
Frequently asked questions
- What size is Unistrut P1000?
- 41 × 41 mm (41.3 mm nominal), 2.5 mm thick, with a 22 mm slot. It weighs about 2.9 kg/m galvanised.
- Why are there no AS 4100 capacities for strut channel?
- It is a thin cold-formed section, designed to AS/NZS 4600. Use the manufacturer's beam and column load tables, which also cover the channel nuts and fittings.
Relevant Australian Standards
- AS/NZS 4600:2018 Cold-formed steel structures
The design Standard for thin-walled cold-formed members such as C and Z purlins and light-gauge framing. - AS/NZS 1170 series Structural design actions
Defines dead, live (1170.1), wind (1170.2), snow (1170.3) and earthquake (AS 1170.4) actions and the load combinations (1170.0) that produce the design actions resisted by the capacities shown here.